FDR Inverter High Static Pressure Duct Split Type (Metal Blower Series)
Specifications
Model
Indoor Unit
FDR250QY1
Cooling Capacity
28.9 kW
99,000 Btu/h
Power Supply
3Ø, 380-415V, 50Hz
Outdoor Unit
RZUR250QY1
Power Consumption
Cooling: 10.7 kW
Indoor Unit
Airflow Rate
Cooling: 78 m³/min
Sound Level
Cooling: 57 dB(A)
Weight
106 kg
External Static Pressure
98 Pa
Dimensions (H x W x D)
500 x 1,330 x 850 mm
Outdoor Unit
Dimensions (H x W x D)
1,657 x 930 x 765 mm
Piping Connections
Gas: Ø22.2 mm
Liquid: Ø9.5 mm
Max. Height Difference
50 m
Weight
185 kg
Max. Piping Length
70 m
Accessories/Functions
Remote Controller Model (Wired)
BRC2E61 (optional) / BRC1E63 (optional)
Remarks
The data are based on the conditions below:
Cooling: indoor temp. 27°CDB/19°CWB; outdoor temp. 35°CDB/24°CWB
Piping length: 7.5m; level difference: 0m
Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.