FVPR Inverter Air Cooled Packaged Split Type
Specifications
Model
Indoor Unit
FVPR450QY1
Cooling Capacity
52 kW
177,000 Btu/h
Power Supply
indoor: 3Ø, 380-415V, 50Hz / outdoor: 3Ø, 380-415V, 50Hz
Outdoor Unit
RZUR450QY1
Power Consumption
Cooling: 20 kW
Indoor Unit
Airflow Rate
Cooling: 166 m³/min
Sound Level
Cooling: 66 dB(A)
Weight
297 kg
External Static Pressure
150 Pa
Dimensions (H x W x D)
1,870 x 1,810 x 720 mm
Outdoor Unit
Dimensions (H x W x D)
1,657 x 1,240 x 765 mm
Piping Connections
Gas: Ø28.6 mm
Liquid: Ø15.9 mm
Max. Height Difference
50 m
Weight
291 kg
Max. Piping Length
70 m
Remarks
The data are based on the conditions below:
Cooling: indoor temp. 27°CDB/19°CWB; outdoor temp. 35°CDB/24°CWB
Piping length: 7.5m; level difference: 0m
Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions and oil recovery mode.