DX Coil HRV Heat Reclaim Ventilation (R410A)
|
|
|
Model |
|
|
VKM50GAV1 |
|
VKM80GAV1 |
|
VKM100GAV1 |
|
 |
| |
Temp. Exchange Efficency
(H/L)
|
% |
|
76/77.5 |
|
78/79 |
|
74/76.5 |
|
 |
| |
Enthalpy EXchange
Efficiency (H/L)
|
|
|
|
|
|
|
|
|
 |
| |
cooling |
% |
|
64/67
|
|
66/68 |
|
62/66
|
|
 |
| |
heating |
% |
|
67/69 |
|
71/73 |
|
65/69 |
|
 |
| |
Cooling capacity |
kW |
|
2.8 |
|
4.5 |
|
5.6 |
|
 |
| |
Heating capacity |
kW |
|
3.2 |
|
5 |
|
6.4 |
|
 |
| |
Dimensions (HxWxD) |
mm |
|
387x1,764x832 |
|
387x1,764x1,214 |
|
387x1,764x1,214 |
|
 |
| |
Machine weight |
kg |
|
96 |
|
109 |
|
114 |
|
|
|
| |
| |
|
|
| |
DX Coil HRV Heat Reclaim Ventilation (R410A)
|
|
|
Model |
|
|
VKM50GMAV1 |
|
VKM80GMAV1 |
|
VKM100GMAV1 |
|
 |
| |
Temp. Exchange Efficency
(H/L)
|
% |
|
76/77.5 |
|
78/79 |
|
74/76.5 |
|
 |
| |
Enthalpy Exchange
Efficiency (H/L)
|
|
|
|
|
|
|
|
|
 |
| |
cooling |
% |
|
64/67
|
|
66/68 |
|
62/66
|
|
 |
| |
heating |
% |
|
67/69 |
|
71/73 |
|
65/69 |
|
 |
| |
Cooling capacity |
kW |
|
2.8 |
|
4.5 |
|
5.6 |
|
 |
| |
Heating capacity |
kW |
|
3.2 |
|
5 |
|
6.4 |
|
 |
| |
Humidification capacity |
kg/h |
|
2.7 |
|
4.0 |
|
5.4 |
|
 |
| |
Dimensions (HxWxD) |
mm |
|
387x1,764x832 |
|
387x1,764x1,214 |
|
387x1,764x1,214 |
|
 |
| |
Machine weight |
kg |
|
102 |
|
120 |
|
125 |
|
|
|
| |
|
|
| |
|
|
|